Description
ICM Controls ICM6501 Air Handler Control
Fan Blower Controls
ClimaTek Air Handling Replacement Control
The ICM6501 air handler control board operates with hot water heating systems. When the thermostat calls for Heat, the control will energize the Water Pump, Valve and Boiler. The blower will energize at the selected speed after 90 seconds to allow the coil to preheat.
DETAILS:
- Controls the water pump, valve, fan and boiler in a hot water heating
system - Jumper selectable high and low speed fan speed selection for 2 speed
blower operations - Integral fan delays for both heating and standard fan operation
- Monitors safety switches including the pressure switch and freeze
protection switch - Test mode feature for system diagnostic purposes
- LED status Light to aid in diagnosing power issues
SPECIFICATIONS:
Input Voltage
24 VAC, 120/240 VAC, 50/60 Hz
Valve Output
24 VAC, 50/60 Hz, 5A
Blower Fan
120/240 VAC, 50/60 Hz, 9.8 FLA
Water Pump
120/240 VAC, 50/60 Hz, 1.5 FLA
Boiler
24 VAC, 50/60 Hz, 5A
Timing
Fan on delay: 0 secs, Fan off delay: 45 secs, Heat fan
on delay: 90 secs, Heat fan off delay: 20 secs
Surrounding Air Temperature Rating:
-40ºF to 167ºF (-40ºC to 75ºC)